OAR 411-054-0300 (8) Heating and Ventilation (8) HEATING AND VENTILATION SYSTEMS. An ALF must have heating and ventilation systems that comply with the building codes in effect at the time of facility construction. (a) TEMPERATURE. For all areas occupied by residents, design temperature for construction must be 75 degrees Fahrenheit. (A) An ALF must provide heating systems capable of maintaining 70 degrees Fahrenheit in resident areas. Required minimum temperatures are no less than 70 degrees Fahrenheit during the day and 60 degrees Fahrenheit during sleeping hours. (B) During times of extreme summer heat, fans must be made available when air conditioning is not provided. (C) Each unit must have individual thermostatic heating controls. (b) EXHAUST SYSTEMS. All toilet and shower rooms must be equipped with a mechanical exhaust fan or central exhaust system that discharges to the outside. (c) WALL HEATERS. Covers, grates, or screens of wall heaters and associated heating elements may not exceed 120 degrees Fahrenheit when they are installed in locations that are subject to incidental contact by individuals or with combustible material. Effective 01/15/2015 wall heaters are not acceptable in new construction or remodeling. (d) VENTILATION. Ventilation in each unit must occur via an open window to the outside, or with a mechanical venting system capable of providing two air changes per hour with one-fifth of the air supply taken from the outside. This Rule is not met as evidenced by: Based on observation and interview, it was determined the facility failed to ensure covers, grates, or screens of wall heaters and associated heating elements did not exceed 120 degrees F when they were installed in locations that were subject to incidental contact by residents or with combustible material for all units of the facility. Findings include, but are not limited to: On 10/19/26 at 9:46 am, an environmental tour was conducted, and it was determined the facility consisted of two separate buildings, both with one-bedroom and studio units. During this tour, cadet and baseboard heaters were observed in resident units. On 10/20/26 at 12:49 pm, a wall heating unit was assessed and temped at 145.9 degrees F. On 10/21/26 at 10:32 am, Staff 6 (Director of Maintenance) assessed the temperature of wall heating unit covers in resident bedrooms and baseboard heaters in resident bathrooms with the surveyor and determined 3 of 3 heating units assessed were above 120 degrees F. Staff 6 stated each of the two assisted living buildings of the facility had ten one-bedroom units, all with the same wall heaters. Staff 6 also stated every bathroom in resident units had the same baseboard heaters. At 10:53 am, Staff 6 reported all wall and baseboard heating units in both buildings of the facility had been disconnected. The need to ensure covers, grates, or screens of wall heaters and associated heating elements did not exceed 120 degrees F was discussed with Staff 1 (Health Services Administrator) on 10/21/26 at 11:32 am. She acknowledged the findings.
All cadet heaters in rooms and bathrooms were turned off by the breaker to ensure no accidental usage. All apartments still have there primary heat source of the Ptac units so they are not with out a heat source and will maintain the room temp of 70 degrees. 2) Cadet wall units in bedrooms will be replaced. We have ordered a new unit that is supposed to deliver by 11/16/26, unit will be installed by in house team for testing accuracy of temp under 120. If unit works to complainance all others will be orderd the week of 11/16 and installed upon arrival. Bathroom heaters will be kept turned off by breakers. Heaters will be monitored quarterly for tempature. 4. Director or Maintenance, Administrator, and/or designee.