Provider Details

Aging and People with Disabilities

Safety, Oversight and Quality

Oregon Department of Human Services Logo

Print Inspection: RL015075

Provider Information


St Andrews Memory Care Community

7617 SE MAIN ST
Portland, OR 97215

Provider ID
5MA107
Administrator
Alison Athey
Phone
(503) 257-7946
Email
executivedirector@standrewsmc.com

Inspection Details


Date
10/28/2026
Event ID
RL015075
Inspection type(s)
Re-Licensure
Deficiencies cited
2

Citation Details


C0420: Fire and Life Safety: Safety


Scope
L2 Widespread
Visit Number
7 - RL015075 - Visit
Visit Date
10/28/2026
Corrected Date
N/A
Details

OAR 411-054-0090 (1-2) Fire and Life Safety: Safety (1) FIRE DRILLS. All fire drills shall be conducted according to the Oregon Fire Code (OFC). (a) Unannounced fire drills must be conducted and recorded every other month at different times of the day, evening, and night shifts. (b) Fire and life safety instruction to staff must be provided on alternate months. (c) The Fire Authority may develop an alternative fire drill plan for the facility. Any such plan must be submitted to the Department. (d) A written fire drill record must be kept to document fire drills that include: (A) Date and time of day; (B) Location of simulated fire origin; (C) The escape route used; (D) Problems encountered and comments relating to residents who resisted or failed to participate in the drills; (E) Evacuation time period needed; (F) Staff members on duty and participating; and (G) Number of occupants evacuated. (e) Alternate exit routes must be used during fire drills to react to varying potential fire origin points. (f) The evacuation capability of the residents and staff is a function of both the ability of the residents to evacuate and the assistance provided by the staff. (g) Staff must provide fire evacuation assistance to residents from the building to a designated point of safety as determined by the Fire Authority having jurisdiction. Points of safety may include, outside the building, through a horizontal exit, or other areas as determined by the Fire Authority having jurisdiction. (h) The fire alarm system shall be activated during each fire drill, unless otherwise directed by the Fire Authority having jurisdiction. (2) If the facility is unable to meet the applicable evacuation level, the facility must make an immediate effort to make changes to ensure the evacuation standard is met. Changes must include, but not be limited to: (a) Increasing staff levels, (b) Changing staff assignments, (c) Requesting change in resident rooms, and (d) Arranging for special equipment. After making necessary changes, if the facility fails to meet the applicable evacuation level, the facility must issue an involuntary move-out notice to the residents in accordance with OAR 411-054-0080. This Rule is not met as evidenced by: Based on interview and record review, it was determined the facility failed to conduct and document fire drills according to the Oregon Fire Code (OFC) with all required elements. Findings include, but are not limited to: On 10/28/26, fire drill records from 05/2026 through 10/2026 were reviewed, and the following was identified: a. The facility failed to conduct unannounced fire drills every other month; b. The facility failed to conduct fire drills at different times of the day, evening and night shifts. c. The facility failed to consistently document the following: * Escape route used; * Evacuation time-period needed; * Problems encountered and comments relating to residents who resisted or failed to participate in the drills; and * Evidence of alternate exit routes used. In an interview on 10/28/26 at 10:08 am, Staff 3 (Maintenance Director) acknowledged the facility failed to perform fire drills on night shift and had not consistently documented the time-period needed for evacuation, escape route used, problems encountered and comments relating to residents who resisted or failed to participate in the drills or evidence of alternate exit routes used. The need to ensure the facility conducted and documented fire drills according to the OFC with all required elements was reviewed with Staff 3 on 10/28/26 at 10:08 am and Staff 1 (ED), Staff 2 (Nurse Consultant), Staff 4 (Director of Operations), Staff 5 (Regional Operations) and Staff 6 (Lead Nurse Consultant) on 10/28/26 at 1:45 pm. They acknowledged the findings.

Z0142: Administration Compliance


Scope
L2 Widespread
Visit Number
7 - RL015075 - Visit
Visit Date
10/28/2026
Corrected Date
N/A
Details

OAR 411-057-0140(2) Administration Compliance (2) The licensee of a memory care community must comply with both the licensing rules for the facility and Chapter 411, Division 57. This Rule is not met as evidenced by: Based on observation, interview, and record review, it was determined the facility failed to follow licensing rules for Residential Care and Assisted Living Facilities. Findings include, but are not limited to: Refer to C 420.